Ultrasonik Sensör Pepperl Fuchs UC2000-30GM-E7R2-V15
5 Aralık 2018
Ultrasonik Sensör Pepperl Fuchs UC2000-30GM-IUEP-IO-V15
5 Aralık 2018Ultrasonik Sensör Pepperl Fuchs UC2000-30GM-IU-V1-HB
Sensör
Ultrasonic Sensor
Ultrasonik Sensör
Pepperl Fuchs
Pepperl Fuchs Sensör
Pepperl Fuchs Ultrasonic Sensor
Pepperl Fuchs Ultrasonik Sensör
Pepperl Fuchs UC2000-30GM-IU-V1-HB
Pepperl UC2000-30GM-IU-V1-HB
Açıklama
Pepperl Fuchs UC2000-30GM-IU-V1-HB Ultrasonik Sensör
Pepperl UC2000-30GM-IU-V1-HB Ultrasonic Sensor
Teknik veriler UC2000-30GM-IU-V1-HB
| Ürün Açıklaması |
| Single head system |
| General specifications | ||
| Sensing range | 80 … 2000 mm | |
| Adjustment range | 120 … 2000 mm | |
| Dead band | 0 … 80 mm | |
| Standard target plate | 100 mm x 100 mm | |
| Transducer frequency | approx. 180 kHz | |
| Response delay | 65 ms minimum 195 ms factory setting |
|
| Indicators/operating means | ||
| LED green | solid: Power-on flashing: Standby mode or program function object detected |
|
| LED yellow 1 | solid: object in evaluation range flashing: program function |
|
| LED yellow 2 | solid: object in detection range flashing: program function |
|
| LED red | solid: temperature/program plug not connected flashing: fault or program function object not detected |
|
| Temperature/TEACH-IN connector | Temperature compensation , Evaluation range programming , output function setting | |
| Electrical specifications | ||
| Operating voltage | 10 … 30 V DC , ripple 10 %SS | |
| Power consumption | ≤ 900 mW | |
| Interface | ||
| Interface type | RS 232, 9600 Bit/s , no parity, 8 data bits, 1 stop bit | |
| Input/Output | ||
| Synchronization frequency | ||
| Common mode operation | max. 30 Hz | |
| Multiplex operation | ≤ 30/n Hz, n = number of sensors | |
| Output | ||
| Output type | 1 current output 4 … 20 mA 1 voltage output 0 … 10 V |
|
| Resolution | evaluation range [mm]/4000, but ≥ 0.35 mm | |
| Deviation of the characteristic curve | ≤ 0.2 % of full-scale value | |
| Repeat accuracy | ≤ 0.1 % of full-scale value | |
| Load impedance | current output: ≤ 500 Ohm voltage output: ≥ 1000 Ohm |
|
| Temperature influence | ≤ 2 % from full-scale value (with temperature compensation) ≤ 0.2 %/K (without temperature compensation) |
|
| Compliance with standards and directives | ||
| Standard conformity | ||
| Standards | EN 60947-5-2:2007 IEC 60947-5-2:2007 EN 60947-5-7:2003 IEC 60947-5-7:2003 |
|
| Standard conformity | ||
| Standards | EN 60947-5-2 | |
| Approvals and certificates | ||
| UL approval | all Div 2 hazardous areas | |
| CSA approval | NRTL certified all Div 2, Class II Div 1, Class III Div 1 hazardous areas |
|
| CCC approval | CCC approval / marking not required for products rated ≤36 V | |
| Ambient conditions | ||
| Ambient temperature | -25 … 70 °C (-13 … 158 °F) | |
| Storage temperature | -40 … 85 °C (-40 … 185 °F) | |
| Mechanical specifications | ||
| Connection type | Cable connector , M12 x 1 , 5-pin , 4-wire | |
| Degree of protection | IP65 | |
| Material | ||
| Housing | 1.4303 stainless steel plastic parts PBT |
|
| Transducer | epoxy resin/hollow glass sphere mixture; polyurethane foam | |
| Note | Individual components: UC-2000-30GM-IUR2-V15; V1-G-2M-PVC; M-106 impact adapter; ADAPT-ALUM*-M30X1/2″ NPT/HB**** | |